PyroFend®, a phenolic resin
based material, has unique protection properties keeping fire,
water and thermal penetration to a minimum. It is completely
non-toxic during fire conditions, lightweight and can be molded
to suit any configuration and application. |
 |
This is a 30mm PyroFend® sample after exposure to a 1700°F
(927°C) fire for one hour.
To view an enlarged graphic, click on the image.
PyroFend
Independent Test Results Features
and Benefits
FireSafe Innovations' unique
lightweight technology,
PyroFend®, can be cast to any shape
or form. PyroFend® features
include:
- Lightweight
- High temperature resistance
- High mechanical strength
- Very low smoke
- Passive fire resistant panels,
enclosures, hybrids, layered composites, and
sandwich panels.
|
PyroFend® can also be used as an adhesive
forming a chemical bond between many materials. FSI utilizes PyroFend® as
our lightweight technology and is currently used in
or is in testing in the following markets:
HVAC
|
Standard EU Tests |
Security
|
Standard EU Tests |
Marine
|
MIL-STD-2031 |
Aviation,
Aerospace & Transportation
|
FAR
25.853, OSU Heat Release, NBS Smoke Density, Toxicity Draeger
Tube |
Office Products
|
UL and Swedish Standard Tests |
Building & Construction
|
ASTM E119 3 Hour Fire Wall
Test |
PyroFend® Independent
Test Results
FAA Flammability Certificate - FAR 25.853 (a) Vertical
Burn
Burn Time |
0 |
Burning Length |
1.1 |
Longest Burning Particle |
None |
FAA Flammability Certificate - FAR 25.853 (a) Horizontal Burn
Results |
Does Not
Ignite |
Average
Burn Rate |
0 |
FAA Flammability Certificate - FAR 25.853 (a) 45 Degree Burn,
BSS-7230 F5
Burning
Time (Sec) |
0 |
Glow Time (Sec) |
0 |
Penetration |
None |
FAA Flammability Certificate - Ohio State Heat Release FAR 25.853
(d)
2
Minute Total |
3 |
Peak
HR |
4 |
Peak
Time (Min) |
3.04 |
Melting |
No |
Sagging |
No |
Dripping |
No |
NBS Smoke Density - ASTM F814/E662 Flaming Mode
Ds@
1.5m |
31 |
Ds@
4.0m |
91 |
DsMax |
91 |
Dmax
Time |
3.59 |
ABD0031,
BSS 7238 |
Pass |
NBS Smoke Density - ASTM F814/E662 Non-Flaming Mode
Ds@
1.5m |
6 |
Ds@
4.0m |
35 |
DsMax |
36 |
Dmax
Time |
3.54 |
ABD0031,
BSS 7238 |
Pass |
TOXICITY Draeger Tube - ABD0031 AITM 3.0005 Flaming Mode
| Gases |
Allowed Limits @
4 Min. (ppm) |
Test Results Flaming (ppm) |
HCN |
150 |
3 |
CO |
1000 |
75 |
NO/NO2 |
100 |
5 |
S02/H2S |
100 |
<1 |
HF |
100 |
60 |
HCL |
150 |
10 |
TOXICITY Draeger Tube - ABD0031 AITM 3.0005 Non-Flaming Mode
| Gases |
Allowed
Limits @
4 Min. (ppm) |
Test
Results Flaming (ppm) |
HCN |
150 |
<1 |
CO |
1000 |
25 |
NO/NO2 |
100 |
<1 |
S02/H2S |
100 |
<1 |
HF |
100 |
2 |
HCL |
150 |
1 |
ASTM E1354/ISO 5660 CONE CALORIMETER TEST
kW/m2
Heat Flux
|
Thickness (mm) |
Time to Ignition
(s)
|
Peak HRR (kW/m2) |
Time to Peak HRR
(s) |
Avg HRR (kW/m2) |
Total Heat Release
MJ/m2
|
Total Smoke Release
m2/m2
|
Avg EFF Heat of Comb.
MJ/kg
|
MAHRE
(kW/m2)
|
FIGRA |
| 50 |
25.4 |
n/a |
8 |
28 |
1 |
0.8 |
62 |
0.2 |
3 |
0.29 |
| 50 |
25.4 |
n/a |
8 |
10 |
2 |
0.6 |
50 |
0.7 |
5 |
0.80 |
| 50 |
25.4 |
n/a |
8.1 |
19.0 |
1.6 |
0.7 |
55.7 |
0.5 |
4.1 |
0.50 |
| 75 |
25.4 |
n/a |
36 |
42 |
1 |
2.1 |
39 |
0.2 |
29 |
0.85 |
| 75 |
25.4 |
n/a |
13 |
864 |
6 |
5.0 |
76 |
1.6 |
6 |
0.01 |
| 75 |
25.4 |
n/a |
24.2 |
453.0 |
3.3 |
3.6 |
57.7 |
0.9 |
17.5 |
0.40 |
| 100 |
25.4 |
73 |
33 |
88 |
21 |
11.0 |
12 |
4.2 |
19 |
0.38 |
| 100 |
25.4 |
70 |
28 |
88 |
19 |
9.8 |
10 |
3.8 |
17 |
0.31 |
| 100 |
25.4 |
63 |
37 |
80 |
20 |
10.6 |
6 |
4.0 |
18 |
0.46 |
| 100 |
25.4 |
68.7 |
32.56 |
85.3 |
20.1 |
10.5 |
8.9 |
4.0 |
18.2 |
0.40 |
PyroFend® Feature & Benefit
Summary
To include your application for PyroFend®, please Contact
Us and include an explanation
so we can serve your fire protection needs.
|
|